HOMEPRODUCTSCOMPOSITE CABLES

 

Composite Cables

 

2XURM70 Coaxial Cable + 2X1P2.5 Power Cable + 2X1PX22AWG Screened Twisted Pair Cable SWB LSZH Sheathed Composite Cable


Application:

CCTV composite cable armoured CCTV composite cable is mainly used in the CCTV application connection. It canbe used to connect the CCTV control system to the CCTV cameras. The steel armour braiding provides added protection to the cable while the LSZH outer jacket provides flame-retardant capability in the event of a fire breakout.

Construction:

2XURM70 Coaxial Cable + 2X1P2.5 Power Cable + 2X1PX22AWG Screened Twisted Pair Cable SWB LSZH

2XURM70 75Ohm Coaxial Cable

Conductor:7/0.2mm Stranded bare or tinned copper conductor, φ 0.6 mm ± 0.02 mm

Insulation:Polyethylene. φ 3.25 mm ± 0.15 mm

Screen:Copper wire braid, coverage 91 % ± 4 %

Sheath:Black LSZH. Nominal overall diameter 5.8 mm ± 0.25 mm

2X1P2.5mm² Power Cable 300V

Conductor:2.5mm² Stranded bare or tinned copper conductor

Insulation:0.6mm LSZH, Red/Blue & Green/Yellow

Screen:Aluminum/polyester tape with 0.5mm² tinned copper drain wire

2X1P22AWG Screened Twisted Pair Cable (Belden 8723 Equivelant)

Conductor:7/0.254mm Stranded bare or tinned copper conductor

Insulation:0.23mm PP, White/Blue & White/Orange

Screen:Aluminum/polyester tape with 24AWG tinned copper drain wire

Element Assembly

Filler:PE or PP material if necessary

Wrapping Tape:Polyester tape or woven tape

Screen:Aluminum/polyester tape with 0.5mm² tinned copper drain wire

Inner Sheath:1.0mm Black LSZH

Armor:0.3mm Galvanized steel wire braid, coverage 85%

Outer Sheath:1.5mm LSZH, nominal overall diameter 25.0 mm ± 2.0 mm

Sheath Color:Orange. Other color available as per requested

Electrical and Physical Properties@20°C:

Coaxial Cable

Max. Conductor Resistance @ 20°C : 92 Ω/km

Impedance: 75±5Ohm (@1MHz)

Max. Attenuation: 15.2dB/100m @100MHz

Power Cable

Conductor Resistance @ 20°C: 7.41Ohm/km

Min. Insulation Resistance: 10 MOhmxkm

Screened Twisted Pair Cable

Electrical Resistance: 49Ohm/km

Min. Insulation Resistance: 1000 MOhmxkm

Note: Other configurations, sizes, colors and length not specified herein are available upon request.